Washington County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5792 Cedar Hollow Way

Approved

Filed Jun 22, 2023 by Jamie Ashby, Summit Backflow Testing · filed from phone

Report

Date of service
Jun 22, 2023
Assembly type
RP
Serial number
W956868
Size
1
Test gauge serial
G-8736
Gauge calibration date
Dec 22, 2022
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 143-74-01111
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5792 Cedar Hollow Way
Owner: Casey Kessler
Parcel 143-74-01111