← Backflow review queue
Backflow assembly test · 8197 Meadow Lark Trl
Needs reviewFiled Nov 25, 2026 by Jamie Ashby, Summit Backflow Testing · filed from phone
Report
- Date of service
- Nov 25, 2026
- Assembly type
- RP
- Serial number
- W280543
- Size
- 1
- Test gauge serial
- G-1789
- Gauge calibration date
- Apr 19, 2026
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 143-47-01260
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
8197 Meadow Lark Trl
Owner: Jamie Kessler
Parcel 143-47-01260