Backflow assembly test · 3499 Sycamore Ct
ApprovedFiled Sep 4, 2025 by Hayden Okafor, Northstar Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Sep 4, 2025
- Assembly type
- DC
- Serial number
- B230501
- Size
- 3/4
- Test gauge serial
- G-3938
- Gauge calibration date
- Apr 22, 2025
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-88-01332
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.