Needs reviewFiled Nov 25, 2026 by Hayden Okafor, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Nov 25, 2026
- Assembly type
- PVB
- Serial number
- B167097
- Size
- 1
- Test gauge serial
- G-5951
- Gauge calibration date
- Jul 28, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-29-01121
- Readings in range, no flags
- Result: passing. Next due date resets when approved.