Sebastian County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4280 Hickory Way

Approved

Filed Apr 23, 2026 by Hayden Pruitt, Summit Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Apr 23, 2026
Assembly type
RP
Serial number
B353690
Size
1
Test gauge serial
G-4896
Gauge calibration date
Dec 14, 2025
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-34-01087
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

4280 Hickory Way
Owner: Parker Nguyen
Parcel 131-34-01087