← Backflow review queue
Backflow assembly test · Corner Brewing Co
ApprovedFiled Feb 8, 2024 by Hayden Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Feb 8, 2024
- Assembly type
- RP
- Serial number
- W276435
- Size
- 2
- Test gauge serial
- G-8971
- Gauge calibration date
- Oct 26, 2023
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-93-01204
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4830 Laurel Rd
Owner: Ramirez Holdings LLC
Parcel 131-93-01204