Backflow assembly test · 6018 Mill Creek Ct
ApprovedFiled Oct 8, 2026 by Hayden Pruitt, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 8, 2026
- Assembly type
- RP
- Serial number
- Z496493
- Size
- 1
- Test gauge serial
- G-4503
- Gauge calibration date
- Jun 29, 2026
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-97-01257
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.