Backflow assembly test · 226 Turkey Hill Way
ApprovedFiled Jan 12, 2025 by Drew Vance, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 12, 2025
- Assembly type
- DC
- Serial number
- W609270
- Size
- 1
- Test gauge serial
- G-5610
- Gauge calibration date
- Jan 27, 2024
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 045-74-01257
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.