Faulkner County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7334 Laurel Rd

Approved

Filed Mar 10, 2024 by Cameron Whitcomb, Patriot Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Mar 10, 2024
Assembly type
DC
Serial number
Z731680
Size
3/4
Test gauge serial
G-5606
Gauge calibration date
Oct 13, 2023
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 045-65-01203
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7334 Laurel Rd
Owner: Emerson Lindqvist
Parcel 045-65-01203