← Backflow review queue
Backflow assembly test · 4035 Stone Gate Trl
ApprovedFiled Dec 13, 2025 by Reese Ellery, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 13, 2025
- Assembly type
- PVB
- Serial number
- W965820
- Size
- 3/4
- Test gauge serial
- G-1222
- Gauge calibration date
- Aug 23, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 045-89-01254
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4035 Stone Gate Trl
Owner: Casey Calloway
Parcel 045-89-01254