Backflow assembly test · 7320 Quarry Dr
ApprovedFiled Jun 30, 2025 by Cameron Whitcomb, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 30, 2025
- Assembly type
- DC
- Serial number
- W334815
- Size
- 3/4
- Test gauge serial
- G-9099
- Gauge calibration date
- Nov 15, 2024
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 045-63-01273
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.