← Backflow review queue
Backflow assembly test · Corner Medical Offices
ApprovedFiled Mar 8, 2026 by Reese Ellery, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 8, 2026
- Assembly type
- DC
- Serial number
- A332613
- Size
- 2
- Test gauge serial
- G-2761
- Gauge calibration date
- Feb 5, 2026
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 045-58-01182
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2561 Quarry Rd
Owner: Benton Holdings LLC
Parcel 045-58-01182