Faulkner County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Corner Elementary School

Approved

Filed Feb 28, 2026 by Cameron Whitcomb, Patriot Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Feb 28, 2026
Assembly type
RP
Serial number
B691961
Size
1 1/2
Test gauge serial
G-7605
Gauge calibration date
Dec 20, 2025
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 045-24-01164
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6175 Hickory Rd
Owner: Fairley Holdings LLC
Parcel 045-24-01164