← Backflow review queue
Backflow assembly test · 5004 Cedar Hollow Rd
ApprovedFiled Apr 27, 2026 by Drew Vance, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 27, 2026
- Assembly type
- PVB
- Serial number
- W637977
- Size
- 1
- Test gauge serial
- G-5125
- Gauge calibration date
- Oct 19, 2025
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 045-14-01213
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
5004 Cedar Hollow Rd
Owner: Drew Okafor
Parcel 045-14-01213