Benton County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Grill

Filed Nov 26, 2026 by Jamie Wexler, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Nov 26, 2026
Assembly type
RP
Serial number
W347786
Size
1 1/2
Test gauge serial
G-3533
Gauge calibration date
Jul 1, 2026
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 007-14-01328
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

7687 Orchard Trl
Owner: Harlow Holdings LLC
Parcel 007-14-01328