Backflow assembly test · Hilltop Grill
ApprovedFiled Jun 6, 2025 by Sam Fairley, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 6, 2025
- Assembly type
- RP
- Serial number
- B881226
- Size
- 1 1/2
- Test gauge serial
- G-3536
- Gauge calibration date
- Oct 9, 2024
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-31-01356
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1309 Pine Knoll Way
Owner: Harlow Holdings LLC
Parcel 007-31-01356