Backflow assembly test · Corner Market

Approved

Filed May 10, 2025 by Emerson Brandt, Clearwater Backflow Testing · filed from phone

Report

Date of service
May 10, 2025
Assembly type
RP
Serial number
B828295
Size
2
Test gauge serial
G-4825
Gauge calibration date
Apr 10, 2025
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 007-83-01007
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.