Backflow assembly test · Station Medical Offices
ApprovedFiled Jun 15, 2024 by Sam Fairley, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 15, 2024
- Assembly type
- RP
- Serial number
- Z390697
- Size
- 2
- Test gauge serial
- G-5565
- Gauge calibration date
- Apr 3, 2024
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-15-01295
- Readings in range, no flags
- Result: passing. Next due date resets when approved.