Backflow assembly test · Hilltop Apartments
Needs reviewFiled Nov 18, 2026 by Sam Fairley, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 18, 2026
- Assembly type
- RP
- Serial number
- A255214
- Size
- 2
- Test gauge serial
- G-1361
- Gauge calibration date
- Jul 31, 2026
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-59-01225
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
5520 Meadow Lark Rd
Owner: Marsh Holdings LLC
Parcel 007-59-01225