← Backflow review queue

Backflow assembly test · Corner Taqueria

Approved

Filed Jun 30, 2024 by Sam Fairley, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Jun 30, 2024
Assembly type
RP
Serial number
Z342849
Size
4
Test gauge serial
G-9061
Gauge calibration date
Feb 22, 2023
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
3.1 psid
Relief valve opened at
2.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 007-53-01206
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.