ApprovedFiled Nov 6, 2025 by Emerson Brandt, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Nov 6, 2025
- Assembly type
- DC
- Serial number
- W521024
- Size
- 1
- Test gauge serial
- G-9063
- Gauge calibration date
- Aug 10, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-88-01054
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.