Backflow assembly test · Hilltop Medical Offices
ApprovedFiled Oct 13, 2025 by Jordan Pruitt, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Oct 13, 2025
- Assembly type
- RP
- Serial number
- A871316
- Size
- 1
- Test gauge serial
- G-9036
- Gauge calibration date
- Jan 22, 2025
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-66-01351
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1368 Cedar Hollow Rd
Owner: Vance Holdings LLC
Parcel 027-66-01351