Yuma County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Medical Offices

Approved

Filed Oct 11, 2024 by Quinn Wexler, Keystone Backflow Testing · filed from phone

Report

Date of service
Oct 11, 2024
Assembly type
RP
Serial number
A871316
Size
1
Test gauge serial
G-2262
Gauge calibration date
Jul 30, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 027-66-01351
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1368 Cedar Hollow Rd
Owner: Vance Holdings LLC
Parcel 027-66-01351