← Backflow review queue
Backflow assembly test · 5610 Mill Creek Ln
ApprovedFiled Sep 25, 2026 by Quinn Wexler, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Sep 25, 2026
- Assembly type
- RP
- Serial number
- A585619
- Size
- 3/4
- Test gauge serial
- G-7151
- Gauge calibration date
- Jan 7, 2026
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-62-01078
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5610 Mill Creek Ln
Owner: Avery Kessler
Parcel 027-62-01078