Yuma County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Diner

Approved

Filed Nov 20, 2024 by Cameron Danner, Lakeside Plumbing & Backflow · filed from phone

Report

Date of service
Nov 20, 2024
Assembly type
RP
Serial number
Z871861
Size
2
Test gauge serial
G-3361
Gauge calibration date
Oct 18, 2024
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 027-78-01070
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1724 Laurel Dr
Owner: Pruitt Holdings LLC
Parcel 027-78-01070