Yuma County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5931 Turkey Hill Way

Approved

Filed Jul 23, 2025 by Jordan Pruitt, Keystone Backflow Testing · filed from phone

Report

Date of service
Jul 23, 2025
Assembly type
RP
Serial number
W427326
Size
1
Test gauge serial
G-1167
Gauge calibration date
Aug 15, 2024
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
3.3 psid
Relief valve opened at
2.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 027-48-01357
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5931 Turkey Hill Way
Owner: Reese Fairley
Parcel 027-48-01357