← Backflow review queue
Backflow assembly test · 5847 Old Church Ct
ApprovedFiled Oct 13, 2025 by Avery Lindqvist, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 13, 2025
- Assembly type
- RP
- Serial number
- Z386573
- Size
- 1
- Test gauge serial
- G-1255
- Gauge calibration date
- Apr 4, 2025
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 4.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-78-01207
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5847 Old Church Ct
Owner: Rowan Ramirez
Parcel 027-78-01207