Yuma County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5847 Old Church Ct

Approved

Filed Oct 9, 2024 by Logan Whitcomb, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Oct 9, 2024
Assembly type
RP
Serial number
Z386573
Size
1
Test gauge serial
G-6365
Gauge calibration date
Sep 2, 2024
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 027-78-01207
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5847 Old Church Ct
Owner: Rowan Ramirez
Parcel 027-78-01207