Backflow assembly test · 554 Cedar Hollow Rd
ApprovedFiled Aug 4, 2025 by Reese Calloway, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 4, 2025
- Assembly type
- DC
- Serial number
- A134171
- Size
- 1
- Test gauge serial
- G-2121
- Gauge calibration date
- Oct 21, 2024
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-49-01226
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
554 Cedar Hollow Rd
Owner: Avery Kessler
Parcel 025-49-01226