Backflow assembly test · Main Street Apartments

Approved

Filed Dec 13, 2025 by Avery Harlow, Valley Backflow Testing · filed from phone

Report

Date of service
Dec 13, 2025
Assembly type
RP
Serial number
A197960
Size
1
Test gauge serial
G-5602
Gauge calibration date
Aug 15, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
3.2 psid
Relief valve opened at
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 025-81-01353
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.