Backflow assembly test · Two Rivers Dental
ApprovedFiled Apr 17, 2024 by Riley Nguyen, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Apr 17, 2024
- Assembly type
- DC
- Serial number
- A130114
- Size
- 1 1/2
- Test gauge serial
- G-8069
- Gauge calibration date
- Aug 18, 2023
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-92-01274
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9200 Hickory Trl
Owner: Fairley Holdings LLC
Parcel 025-92-01274