← Backflow review queue
Backflow assembly test · Station Car Wash
ApprovedFiled Nov 18, 2025 by Riley Nguyen, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Nov 18, 2025
- Assembly type
- RP
- Serial number
- K219798
- Size
- 1
- Test gauge serial
- G-8643
- Gauge calibration date
- Apr 7, 2025
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-23-01282
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3569 Laurel Rd
Owner: Marsh Holdings LLC
Parcel 025-23-01282