Backflow assembly test · Two Rivers Taqueria
Needs reviewFiled Nov 26, 2026 by Riley Nguyen, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Nov 26, 2026
- Assembly type
- RP
- Serial number
- W116203
- Size
- 1 1/2
- Test gauge serial
- G-7288
- Gauge calibration date
- Nov 1, 2025
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-93-01247
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.