Backflow assembly test · 7769 Cedar Hollow Rd

Approved

Filed Dec 10, 2024 by Morgan Stroud, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Dec 10, 2024
Assembly type
RP
Serial number
B157785
Size
3/4
Test gauge serial
G-8123
Gauge calibration date
May 6, 2024
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 021-33-01288
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7769 Cedar Hollow Rd
Owner: Shawn Benton
Parcel 021-33-01288