Pinal County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2065 Meadow Lark Rd

Approved

Filed Dec 3, 2025 by Morgan Stroud, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Dec 3, 2025
Assembly type
RP
Serial number
B326219
Size
3/4
Test gauge serial
G-3726
Gauge calibration date
Apr 29, 2025
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 021-22-01149
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2065 Meadow Lark Rd
Owner: Jordan Vance
Parcel 021-22-01149