← Backflow review queue
Backflow assembly test · 4092 Mill Creek Rd
ApprovedFiled Nov 10, 2026 by Drew Stroud, Clearwater Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 10, 2026
- Assembly type
- RP
- Serial number
- B220327
- Size
- 3/4
- Test gauge serial
- G-6449
- Gauge calibration date
- May 17, 2026
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 021-24-01035
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4092 Mill Creek Rd
Owner: Drew Marsh
Parcel 021-24-01035