Pima County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Dental

Approved

Filed Jan 26, 2025 by Morgan Calloway, Lakeside Plumbing & Backflow · filed from phone

Report

Date of service
Jan 26, 2025
Assembly type
RP
Serial number
Z214248
Size
1
Test gauge serial
G-2222
Gauge calibration date
Nov 4, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-55-01322
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4821 Meadow Lark Rd
Owner: Nguyen Holdings LLC
Parcel 019-55-01322