Pima County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 9611 Hickory Dr

Approved

Filed Oct 7, 2026 by Logan Vance, Lakeside Backflow Testing · filed from phone

Report

Date of service
Oct 7, 2026
Assembly type
PVB
Serial number
Z679009
Size
3/4
Test gauge serial
G-3027
Gauge calibration date
Mar 2, 2026
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-93-01284
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9611 Hickory Dr
Owner: Cameron Fairley
Parcel 019-93-01284