Pima County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5014 Turkey Hill Way

Approved

Filed May 13, 2024 by Logan Vance, Lakeside Backflow Testing · filed from phone

Report

Date of service
May 13, 2024
Assembly type
RP
Serial number
B193845
Size
3/4
Test gauge serial
G-9624
Gauge calibration date
Aug 19, 2023
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-70-01344
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5014 Turkey Hill Way
Owner: Avery Calloway
Parcel 019-70-01344