Backflow assembly test · 6992 Old Church Way
ApprovedFiled Sep 18, 2025 by Sam Brandt, Patriot Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Sep 18, 2025
- Assembly type
- RP
- Serial number
- A978390
- Size
- 1
- Test gauge serial
- G-9232
- Gauge calibration date
- Jan 3, 2025
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 019-17-01181
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.