← Backflow review queue
Backflow assembly test · 2493 Pine Knoll Ln
ApprovedFiled May 20, 2025 by Logan Vance, Lakeside Backflow Testing · filed from phone
Report
- Date of service
- May 20, 2025
- Assembly type
- DC
- Serial number
- B250269
- Size
- 1
- Test gauge serial
- G-2788
- Gauge calibration date
- Jan 27, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 019-52-01171
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2493 Pine Knoll Ln
Owner: Morgan Stroud
Parcel 019-52-01171