Backflow assembly test · 3521 Stone Gate Ct

Approved

Filed Sep 23, 2025 by Logan Vance, Lakeside Backflow Testing · filed from phone

Report

Date of service
Sep 23, 2025
Assembly type
RP
Serial number
W939117
Size
3/4
Test gauge serial
G-4385
Gauge calibration date
Jan 17, 2025
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-56-01187
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3521 Stone Gate Ct
Owner: Drew Hollins
Parcel 019-56-01187