Pima County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Pizza

Approved

Filed Oct 30, 2024 by Jamie Pruitt, Lakeside Backflow Testing · filed from phone

Report

Date of service
Oct 30, 2024
Assembly type
RP
Serial number
W705458
Size
1 1/2
Test gauge serial
G-5569
Gauge calibration date
Jul 17, 2024
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-46-01342
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6888 Hickory Dr
Owner: Pruitt Holdings LLC
Parcel 019-46-01342