Backflow assembly test · 4352 Pine Knoll Ct

Approved

Filed Jan 20, 2026 by Logan Vance, Lakeside Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Jan 20, 2026
Assembly type
RP
Serial number
K118905
Size
1
Test gauge serial
G-6857
Gauge calibration date
Apr 25, 2025
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-37-01138
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4352 Pine Knoll Ct
Owner: Reese Hollins