← Backflow review queue
Backflow assembly test · 2156 Spring Branch Ln
ApprovedFiled Aug 10, 2025 by Taylor Vance, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Aug 10, 2025
- Assembly type
- RP
- Serial number
- Z454297
- Size
- 3/4
- Test gauge serial
- G-3505
- Gauge calibration date
- Jun 8, 2025
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-42-01148
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2156 Spring Branch Ln
Owner: Jordan Ashby
Parcel 005-42-01148