Backflow assembly test · 8116 Pine Knoll Way
ApprovedFiled Nov 28, 2023 by Taylor Benton, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 28, 2023
- Assembly type
- DC
- Serial number
- W326350
- Size
- 3/4
- Test gauge serial
- G-1896
- Gauge calibration date
- Aug 28, 2022
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-10-01174
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.