Coconino County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Main Street Brewing Co

Approved

Filed Jun 9, 2026 by Hayden Stroud, Keystone Backflow Testing · filed from phone

Report

Date of service
Jun 9, 2026
Assembly type
RP
Serial number
Z450606
Size
2
Test gauge serial
G-5139
Gauge calibration date
Nov 14, 2025
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-48-01106
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9897 Laurel Ct
Owner: Whitcomb Holdings LLC
Parcel 005-48-01106