← Backflow review queue
Backflow assembly test · 6973 Mill Creek Trl
ApprovedFiled Jan 6, 2026 by Casey Whitcomb, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 6, 2026
- Assembly type
- DC
- Serial number
- A586896
- Size
- 1
- Test gauge serial
- G-4469
- Gauge calibration date
- Jun 5, 2025
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-96-01118
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6973 Mill Creek Trl
Owner: Avery Ashby
Parcel 073-96-01118