Backflow assembly test · 1922 Mill Creek Ln

Approved

Filed Sep 30, 2025 by Drew Harlow, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Sep 30, 2025
Assembly type
DC
Serial number
K309481
Size
1
Test gauge serial
G-2294
Gauge calibration date
Sep 19, 2024
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
2.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-79-01257
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1922 Mill Creek Ln
Owner: Riley Nguyen
Parcel 073-79-01257