Jefferson County, ALCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Diner

Approved

Filed Nov 13, 2026 by Alex Benton, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Nov 13, 2026
Assembly type
RP
Serial number
B232333
Size
4
Test gauge serial
G-7482
Gauge calibration date
Mar 16, 2026
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-89-01279
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5107 Turkey Hill Way
Owner: Pruitt Holdings LLC
Parcel 073-89-01279